Pressure Systems, Inc. NetScanner™ System (9016, 9021, & 9022) User’s Manual
www.PressureSystems.com
3 - 80
which should be replaced as follows. The sequence ‘T’, ‘I’, and ‘U’ were piecemeal parts of the
(now obsolete) command ‘M,’ which was itself replaced by Read Scaled Analog Inputs (L’).
Also, there is the higher-resolution alternative Read High-Precision Data (‘r’) command. The
piecemeal pair of calibration commands ‘g’ and ‘W’ have always had a complete alternative, the
Calculate and Set Offsets (‘h’) command. Likewise, the other pair of calibration commands ‘X’
and ‘Y’ have always had a complete alternative, the Calculate and Set Gains (‘Z’) command.